Procedural Considerations
Page 54 34-ST-25-20 MC Toolkit User Manual Release 0
7/03
Table 15 Honeywell HART Calibration - Loop Test
Honeywell HART Calibration - Loop Test
Loop Test
This function verifies the
integrity of the physical
components of analog
output loop current in a
process application
To observe output current
levels, connect a voltmeter
or current meter into the
current loop.
Select the desired current
level, then select
Set Output.
Observe the meter, and
select
Yes in the popup
message to command the
transmitter to go to the
selected current level.
To return to the input-
dependent current level,
select
Clear Output; this
popup message appears.
If the Back button is
selected before using the
Clear Output command, the
message at right appears.
To go back to the
Calibration Menu, select
OK in the popup, select the
Clear Output button, then
select the
Back button.