HP ProLiant SL Advanced Power Manager
User Guide
Abstract
This guide provides installation and operation guidance for the HP ProLiant SL Advanced Power Manager. This guide is for the
person who installs,
administers, and troubleshoots servers and storage systems.
Part Number: 574949-008
March 2012
Edition: 8
Przeglądanie stron 0
1 2 3 4 5 6 ... 90 91

Podsumowanie treści

Strona 1 - User Guide

HP ProLiant SL Advanced Power Manager User Guide Abstract This guide provides installation and operation guidance for the HP ProLiant SL Advanced Po

Strona 2

Introduction 10 The total rating of the Intelligent Extension Bar is 16 A. Callout Description 1 Row of green power indicators (one for each ou

Strona 3 - Contents

Introduction 11 2U-chassis, DL2000 Scalable System Enclosure with four half-width 1U nodes Item Description 1 SL-APM 2 DL series enclosure 3 Bay

Strona 4 - Contents 4

Introduction 12 Item Description 4 Bay 3 of a 2U-chassis, SL6000 Scalable System Enclosure with four 1U half-width nodes 4U-chassis, s6500 Scalabl

Strona 5 - Contents 5

Introduction 13 4U-chassis, s6500 Scalable System Enclosure with two 4U half-width nodes Item Description 1 SL-APM 2 SL-APM Distribution Module 3

Strona 6 - Contents 6

Introduction 14 4U-chassis, s6500 Scalable System Enclosure with four 2U half-width nodes Item Description 1 SL-APM 2 SL-APM Distribution Module

Strona 7 - Introduction

Installation and configuration 15 Installation and configuration Prerequisites for installation The SL-APM can be administered through the serial co

Strona 8 - SL-APM rear view

Installation and configuration 16 • Enter the commands manually. This procedure is for advanced users who want more control over the configuration

Strona 9

Installation and configuration 17 11. Save the new configuration. To save the new configuration, select Y. All settings relating to the SL-APM Ether

Strona 10 - Callout Description

Installation and configuration 18 Verifying network communication To verify the network communication is working, enter PING <IP address>, whe

Strona 11

Command Line Interface 19 Command Line Interface Command line conventions CLI input is case insensitive except when otherwise noted. The CLI uses a

Strona 12 - Item Description

© Copyright 2009, 2012 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice. The only warr

Strona 13

Command Line Interface 20 2. When prompted, enter the assigned IP address or FQDN name of SL-APM. 3. Enter Administrator. 4. Enter a valid passwor

Strona 14 - Automatic discovery

Command Line Interface 21 7 : Compute node (active) 8 : Compute node (active) Power s

Strona 15 - Configuring the SL-APM

Command Line Interface 22 1: enabled 2: enabled 3: enabled 4: enabled 5: enabled 6: enabled Input Feed

Strona 16

Command Line Interface 23 Serial #: USE119A2YW 2 : Compute node (active) Asset tag: myserver2 Serial #: USE

Strona 17 - Network configuration

Command Line Interface 24 Amps Drawn : 0.830000 Infeed Status : On Infeed Load Status : Normal 4:

Strona 18 - Security configuration

SL-APM logging 25 SL-APM logging Overview of logging Logging enables you to see the following information in SL-APM • Actions taken • Events • Ti

Strona 19 - Command Line Interface

SL-APM logging 26 003:WED JAN 13 11:03:20 2010: Dist. Module 1, port 5, server 1 was powered off 004:WED JAN 13 11:03:29 2010: Dist. Modul

Strona 20 - Topology and inventory

SL-APM logging 27 External logging To show the syslog server address configuration information, enter SHOW SYSLOG. To set the syslog server address

Strona 21 - Command Line Interface 21

SL-APM logging 28 Fault logged message Description credentials Checksum failure - password credentials Checksum failure while reading account crede

Strona 22 - Showing assetinfo

Power capping 29 Power capping Power capping overview The HP ProLiant SL family of products provides a power capping feature that operates at the se

Strona 23 - Command Line Interface 23

Contents 3 Contents Introduction ...

Strona 24 - Showing the MAC address

Power capping 30 SL-APM management requirements Minimum firmware requirements are: • SL-APM 1.40 • SL Power Management Controller (SL Chassis) enc

Strona 25 - SL-APM logging

Power capping 31 Power capping licensing All servers that are being power capped must have the iLO\LO100 advanced license installed. Before a power

Strona 26 - SL-APM logging 26

Power capping 32 committed to the SL-APM onboard EEPROM so that it becomes persistent when SL-APM is reset during operation. NOTE: The power ba

Strona 27 - SL-APM fault messages

Power capping 33 Are you sure you wish to set a new power baseline for this system? (Y/N/Q) -> Yes Retrieving license information for chassis Pow

Strona 28

Power capping 34 In this example, APM Port (item 1) and DM Port (item 2) are illustrated. > show power baseline APMPort DMPort Serial Number Min

Strona 29 - Power capping

Power capping 35 1 3 6 259 n/a 344 (DC watts) 1 3 7 240 n/a 325 (DC watts) 1 3

Strona 30 - • SL-APM 1.40

Power capping 36 PDM port 1 PDM Port Load ---- ---- ---- 1 1 93 (AC watts) 1 2

Strona 31 - Rack level power capping

Power capping 37 All values listed are in AC watts APMPort DMPort Serial Number Min Cap Max Cap Set Cap Slots Populated ------- ------ ----------

Strona 32 - Power capping 32

Power capping 38 7 (no Dist. Module present) 8 (no Dist. Module present) Total servers = 10 Total chassis = 2 Total fan wattage = 3

Strona 33 - Setting power capping

Power capping 39 Since SL-APM zones are merely definitions of user defined SL-APM group boundaries (and by extension any chassis that are plugged in

Strona 34 - Power capping 34

Contents 4 SL-APM and SL-APM Distribution Module cabling ... 31

Strona 35 - Power capping 35

Power capping 40 1 2 CNK71600K4 585 2372 1500 (8) 2 3 5 7 ------- ------- -------

Strona 36 - Power capping 36

Power capping 41 In the following figure, the SL-APM port 2 is connected to the SL-APM Distribution Module port 4. The distribution module port, in

Strona 37 - Power capping 37

Power capping 42 • A total count of all the servers and chassis listed • Total fan wattage for the listing • Total system wattage in DC watts •

Strona 38

Power capping 43 PDM Port Load ---- ---- ---- 1 (no PDM Extension present) 2 (no PDM Extension present) ---

Strona 39 - Power capping with zones

Power capping 44 The poll cycle time varies depending on how many server chassis are plugged into the SL-APM system. The more chassis that are prese

Strona 40 - Power commands

General commands 45 General commands Working with passwords SL-APM has no factory-assigned password. You can set a password and enable or disable a

Strona 41

General commands 46 When entering a password in this manner, you must include quotation marks around the password being set. This form of command is

Strona 42 - Power capping 42

General commands 47 where: "<username>" is the account username. This command removes the specified account from the system. If the

Strona 43 - Setting power

General commands 48 The parameters enable the addition of all chassis on all SL-APM ports, all the chassis plugged into an SL-APM port through a SL-

Strona 44 - Power capping 44

General commands 49 Showing zones To display all the currently defined zones and their respective member chassis, enter SHOW ZONES. For example: mys

Strona 45 - General commands

Contents 5 Troubleshooting ...

Strona 46 - Working with accounts

General commands 50 o To reset the password, enter SET PASSWORD. For more information, see "Setting SL-APM passwords (on page 45)". o To

Strona 47 - Working with zones

General commands 51 SET NAME "alphabravo" Setting the time To set the time, enter SET TIME <month> <day> <year> <hou

Strona 48 - Removing zones

General commands 52 • Serial Number • FRU File ID Showing the name To show the name, enter SHOW NAME. The name appears. As an example, the follow

Strona 49 - Using the security override

General commands 53 Resetting factory settings To reset the factory settings, enter RESET FACTORY. All configuration and password settings will be l

Strona 50 - Setting the name

Using SNMP 54 Using SNMP SNMP overview The architectural model for SNMP contains these components: • At least one network management station with m

Strona 51 - Showing information

Using SNMP 55 Setting the SNMP read-only community string To set the SNMP read-only community string, enter SET SNMP RO "<community_string&g

Strona 52 - • FRU File ID

Using SNMP 56 • cpqRackPowerSupplyOK • cpqRackPowerSupplyRemoved • cpqRackPowerSupplyInserted • cpqRackServerBladeRemoved • cpqRackServerBladeI

Strona 53 - Resetting factory settings

Firmware 57 Firmware Upgrading the firmware You can perform firmware upgrades using either FTP or TFTP. To perform an upgrade: 1. Place the firmwar

Strona 54 - Using SNMP

Troubleshooting 58 Troubleshooting Alert messages The following messages appear in SL-APM. Message Where this issue occurs Required action There

Strona 55 - Setting the SNMP location

Commands 59 Commands Clear faults • Command: CLEAR FAULTS • Description: Clears the fault log to have 0 entries. Clear log • Command: CLEAR LOG

Strona 56 - Using SNMP 56

Contents 6 Show time ...

Strona 57 - Firmware

Commands 60 Disable telnet • Command: DISABLE TELNET • Description: Turns off telnet access to the SL-APM board. Existing sessions will not be log

Strona 58 - Troubleshooting

Commands 61 • Description: o Adds a new user to the system. A single SL-APM can maintain two login accounts, including the built-in Administrator

Strona 59 - Commands

Commands 62 Exit • Command: EXIT • Description: Same as LOGOUT. Help • Command: HELP • Description: Displays a list of available commands. Log

Strona 60 - Commands 60

Commands 63 Same as RESET. Reset factory WARNING: When you enter RESET FACTORY, SL-APM erases your entire configuration. Before resetting facto

Strona 61 - Enable password

Commands 64 Set name • Command: SET NAME "<name>" • Description: Assigns a name to SL-APM that will appear in the log and syslog e

Strona 62 - Commands 62

Commands 65 ALL is used when the command applies to all nodes. You can also use it when the command applies to all the server nodes in a particular

Strona 63 - Set gateway

Commands 66 • Description: o Sets the system time on the battery-backed clock. o All five parameters must be present. The hour parameter must be

Strona 64 - Set power

Commands 67 percentage is then multiplied against each chassis maximum wattage value to arrive at an appropriate cap value for that individual chass

Strona 65 - Set time

Commands 68 Show log • Command: SHOW LOG • Description: Shows the event log. Show syslog • Command: SHOW SYSLOG • Description: Shows the curren

Strona 66 - Set power cap

Commands 69 SHOW RACK SHOW RACK <PORT#> SHOW RACK <PORT#> <DMPORT#> SHOW RACK ALL where: <PORT#> refers to the SL-APM port.

Strona 67 - Show info

Introduction 7 Introduction SL-APM overview SL-APM is a single point of contact for HP ProLiant Scalable System administration. SL-APM enables: • D

Strona 68 - Show rack

Commands 70 Show asset info • Command: SHOW ASSETINFO SHOW ASSETINFO <PORT#> SHOW ASSETINFO <PORT#> <DMPORT#> where: <PORT#>

Strona 69 - Show topology

Commands 71 Show version • Command: SHOW VERSION SHOW VERSION ALL • Description: o Displays SL-APM firmware copyright, version, build date, and h

Strona 70 - Show power baseline

Commands 72 ADD ZONE my_zone 1 5 Adds the chassis plugged into SL-APM Distribution Module port 5 on SL-APM port 1 to zone MY_ZONE. If MY_ZONE did no

Strona 71 - Upgrade image

Commands 73 Removes one or more chassis from a zone definition. Enable pullpower • Command ENABLE POLLPOWER • Description Enables background proc

Strona 72 - Remove zone

Commands 74 SET SNMP RO "<community_string>" • Description: Sets the SNMP read-only public string to the string specified as a para

Strona 73 - Commands 73

Commands 75 — cpqRackEnclosureInserted — cpqRackEnclosureFanRemoved * — cpqRackEnclosureFanInserted * — cpqRackEnclosureFanFailed — cpqRackEncl

Strona 74 - Set SNMP trapdest

Supported MIB objects 76 Supported MIB objects Supported cpqRack MIB objects Object name Object identifier Notes Compaq 1.3.6.1.4.1.232 — cpqRac

Strona 75 - Commands 75

Supported MIB objects 77 Object name Object identifier Notes cpqRackCommonEnclosureSerialNumPrev 1.3.6.1.4.1.232.22.2.3.1.1.1.24 — cpqRackCommonE

Strona 76 - Supported MIB objects

Supported MIB objects 78 Object name Object identifier Notes cpqRackServerBlade 1.3.6.1.4.1.232.22.2.4.1 — cpqRackSystemTime 1.3.6.1.4.1.232.22.2

Strona 77

Supported MIB objects 79 Object name Object identifier Notes exception of HP ProLiant s6500 Chassis cpqRackEnclosureFanInserted 1.3.6.1.4.1.232.22

Strona 78

Introduction 8 Item Description 7 PDM1 for HP Intelligent Modular PDU Extension Bar 8 PDM2 for HP Intelligent Modular PDU Extension Bar 9 SL-APM Di

Strona 79

Supported MIB objects 80 Object name Object identifier sysContact 1.3.6.1.2.1.1.4 sysName 1.3.6.1.2.1.1.5 sysLocation 1.3.6.1.2.1.1.6 sysServices 1

Strona 80

Supported MIB objects 81 Object name Object identifier ifNumber 1.3.6.1.2.1.2.1 ifNumber 1.3.6.1.2.1.2.1 ifTable 1.3.6.1.2.1.2.2 ifEntry 1.3.6.1.2.

Strona 81

Supported MIB objects 82 Object name Object identifier ipReasmFails 1.3.6.1.2.1.4.16 ipFragOKs 1.3.6.1.2.1.4.17 ipFragFails 1.3.6.1.2.1.4.18 ipFrag

Strona 82

Supported MIB objects 83 Object name Object identifier ipRoutingDiscards 1.3.6.1.2.1.4.23 ipInReceives 1.3.6.1.2.1.4.3 ipInHdrErrors 1.3.6.1.2.1.4.

Strona 83

Supported MIB objects 84 Object name Object identifier icmpInEchoReps 1.3.6.1.2.1.5.9 tcp 1.3.6.1.2.1.6 tcpRtoAlgorithm 1.3.6.1.2.1.6.1 tcpInSegs 1

Strona 84

Supported MIB objects 85 PDU identity table Two new tables are supported in the PDU section of the CPQ POWER MIB. These two tables are supported for

Strona 85 - PDU input table

Support and other resources 86 Support and other resources Before you contact HP Be sure to have the following information available before you call

Strona 86 - Support and other resources

Acronyms and abbreviations 87 Acronyms and abbreviations DHCP Dynamic Host Configuration Protocol FQDN Fully Qualified Domain Name SL-APM HP ProLi

Strona 87 - Acronyms and abbreviations

Documentation feedback 88 Documentation feedback HP is committed to providing documentation that meets your needs. To help us improve the documentat

Strona 88 - Documentation feedback

Index 89 A accessing the CLI 20 ADD ACCOUNT 48, 64 ADD ZONE 40, 49, 75 alert messages 61 authorized reseller 89, 90 automatic discovery

Strona 89 - Index 89

Introduction 9 HP ProLiant SL Advanced Power Manager Distribution Module The distribution module includes a connector bay for the SL-APM and cables

Strona 90 - Index 90

Index 90 external logging 29 F factory settings, restoring 48 firmware, upgrading 60 first-time configuration 15 front panel components 7

Strona 91 - Index 91

Index 91 telephone numbers 89, 90 telnet session 21 topologies 21 troubleshooting 61 W website, HP 90 working with accounts 48 Z zone ov